Avoiding unexpected equipment downtime long-term requires a detailed preventive and predictive program.
A
proper preventive maintenance plan must cover the electric motors and controls
in service within the plant. A correctly designed and implemented program will
help ensure many hours of operation without unexpected downtime of any
equipment.
Following
these suggestions will set the plant on the path to a well-designed program,
which should include the controls portion of the motors system.
Start with a plan
A
good plan compares the costs of preventive maintenance (PM) and unexpected
downtime. It also includes the cost of proper test equipment and tools.
Training for in-house teams is needed for testing to be efficient and thorough.
In some cases, it may be more cost-effective to use outside sources to perform
the more complex tests.
The
plan must be documented; plan implementation can be quantified to ensure that
costs are minimized while the systems are kept in a healthy operational state.
Motor and control center
maintenance
Begin
maintenance with the motor and control center (MCC). This step aims to check
component health, including the motors, starters, protective equipment, and
circuit breakers (see Figure 1). The following tests should be performed
annually or more frequently if the equipment is subjected to severe
environmental issues such as heat or vibration. This will improve motor
performance and help with UL508 conformance.
Figure 1. Start with checking component health, including the motors, starters, protective equipment, and circuit breakers.
Recommended testing and inspection
1. Tighten all electrical connections as the device
manufacturer recommends using a calibrated torque wrench.
2. Perform
thermal imaging on each device—replace
any device that shows hot spots. Be sure to record the results for future
reference.
3. Conduct
an insulation test on all incoming and
outgoing cables.
4. Conduct
an insulation resistance test of all contactors. Test from phase to ground, phase to phase, and
across any open contacts. Ensure that they meet the manufacturer’s
specifications.
5. Clean
all filters and remove any accumulated dust within the enclosure. Do not use compressed air to clean; use a
vacuum or soft cloth. Avoid using spray contact cleaners; they can cause more
issues than they resolve with the pole faces.
6. Check
all disconnect handles and breaker mechanisms for wear and replace them as required.
7. Conduct
a contact resistance test
using the four-wire DC voltage drop method.
8. Measure
the resistance across any fusing and
replace the fuses outside the manufacturer’s recommendations.
If
you do not have the manufacturer’s recommendations on any of the above tests or
inspections, use InterNational Electrical Testing Association (NETA)
recommendations. (For more information visit www.netaworld.org.)
Component maintenance
This
step ensures the motor itself is healthy and in good operating condition.
Proper practices are vital for many years of problem-free motor operation.
Recording all maintenance steps and test results is essential for setting a
baseline and seeing trends that determine when a motor is failing.
Bearing
lubrication requirements vary greatly from motor to motor. Lubrication
intervals are affected by the motor type, its operating rpm and, most
importantly, the environment. Severe environments will require more frequent
lubrication.
The
proper procedure is to clean the grease fitting first, open any purge fittings,
and wipe off the grease fitting when done.
It
is best to use the manufacturer’s recommended grease, but if that isn’t
possible, ensure that the one used is compatible with the original grease.
Never overlubricate. This is one of the top reasons for premature
motor failure.
Inspections
Simple
inspections, such as the following steps, can provide favorable results in
motor health (see Figure 2):
1. Clean excessive dust, dirt, or debris that may have
accumulated on the motor’s frame. A clean motor dissipates heat properly. If
the motor is located in a severe environment and nearly impossible to keep
clean, consider using protective motor covers.
2. As with the MCC testing, check that all electrical connections are tightened to
the manufacturer’s recommendations using a calibrated torque wrench.
3. Visually inspect all power cables and perform a
resistance test. Replace any worn or damaged cables.
4. Periodically remove critical motors on variable
frequency drives (VFDs) from service. If bearing inspection reveals pitting, this signifies shaft current
leaks caused by the pulse with modulation (PWM) sine wave of the VFD. Install shaft grounding rings to mitigate this
problem. Consider upgrading to VFD-rated cable and adding shaft grounding
devices if bearing damage is an ongoing
issue.
Figure 2. Vibration analysis of this motor bearing revealed textbook fluting; it was discovered in time to avoid unpredicted downtime. The motor runs one of a municipality’s vertical turbine pumps feeding fresh water to a community of several thousand households. (Image courtesy Motion.)
Electrical tests
The
following electrical tests need to be performed. For accuracy, the tests must
be conducted by qualified technicians, and all results must be recorded:
1. Winding
phase-to-phase resistance test—Use a low ohm meter; the resistance of each winding should be the
same.
2. IR-to-ground
test—This measures the
resistance between each winding and the frame ground. Use an insulation
resistance tester because of the high resistances expected. It is important to
remember that temperature is a factor in these tests, and the winding
temperature needs to be part of the record, so the resistance can be adjusted
to the 40 °C standard.
3. Surge
tests—Check the incoming and
outgoing surge values. This test will point out insulation weakness, shorts in
the windings, and internal damage or improper connections within the motor. A
multifunction surge tester is needed to perform this test.
4. High
potential (hi-pot) test—This
overvoltage test is used as a stress test for the insulation. Voltages as high
as 75,000 V can be reached. A dc hi-pot tester is required.
5. Polarization
index test—This
insulation-to-ground test is performed over 10 minutes. When completed, the ratio
of the 10-minute value over the 1-minute value is calculated and recorded. The
results can predict insulation failure. This test needs to be conducted to IEEE
43-2000.
Thermal imaging
Thermal
imaging is an important component in preventive maintenance. It can point out
many issues that other tests cannot easily do.
Thermal
surveys of the motor should be scheduled based on its operating
characteristics. However, this should be done at least once annually.
All
surveys need to be recorded and a baseline set. Reviewing the most recent tests
to the baseline will present any impending problems with the motor (see Figure
3).
Figure 3. This thermal inspection of a steel rolling mill motor shows an increased temperature due to a potential faulty bearing or misalignment issue. (Image courtesy Teledyne FLIR.)
Well-trained inside technicians can be used for all the testing and inspections discussed. Each organization is different, with specific needs and cost controls to consider. But in many cases, using an outside certified testing company is more cost-effective. This should be explored if training and equipment costs are prohibitive.
What does the future
hold?
The
advent of the connected world and the industrial internet of things (IIoT) has
caused incredible changes to predictive maintenance. Data collection and thorough analysis are essential for today’s
smart factories to run at top efficiency. Accurately planning maintenance is
based on information directly provided by machines.
A
complete discussion of this process is beyond the scope of this article, but
here are some highlights:
Condition monitoring devices are essential to a modern predictive
maintenance data collection plan. Two kinds of devices provide feedback from
motors to the data collection points and then the data analysis software:
1. Vibration
sensors collect data based on
the vibration of the motor. Over time, this will show a trend line that can
predict bearing failure, shaft alignment issues, or mounting integrity.
2. Temperature
sensors collect data based on
the temperature of the motor. Winding sensors and bearing sensors each provide
data showing trend lines in the motor’s health.
Machine
learning software takes all the data collected and sets the baseline for the
motor and machine. This facilitates the maintenance schedule based on actual
machine usage as opposed to general manufacturer suggestions.
When
the software notices that a temperature or vibration threshold has been
exceeded, different warnings or alarms can be issued to:
1. Turn on a stack light to inform the operator of
a problem.
2. Email the maintenance staff about the issue.
3. Sound an alarm and shut down the machine.
Remember
that a well-planned, executed, and recorded preventive/predictive maintenance
program will ensure a long, reliable life for motors and control systems. Start
with a plan, document, routinely maintain the MCC and other components, and
leverage predictive maintenance tools.
By Ken DeBauche (plantservices.com)
Ken DeBauche is an account representative and electrical specialist at Motion (www.motion.com/plantservices). He has 45 years of industry experience, including 20 with Kaman Distribution Group. DeBauche presents complete solutions to customers, using his deep knowledge of electrical and mechanical power transmission.
Comments
Post a Comment